Navien · Furnace

E774 External safety device on IN_1 stops the furnace

High severity NPF

What the control is telling you

Shown when an external safety device wired to the IN_1 terminal on the sub controller is open at startup. Gas heat and cooling are disabled until the condition is cleared.

Applies to: NPF700 Hydro-furnace with external safety device on IN_1

Likely causes

  • External safety device such as a float switch has actuated
  • Safety device wiring or contact type does not match the furnace setting

Test and repair steps

  1. Turn off power to the furnace.
  2. Check the external safety device (for example the float switch) and correct the condition that tripped it.
  3. Confirm the device wiring at IN_1 and COM and the contact type setting.
  4. Restore power, then press the Back button on the front control panel to reset the furnace.

Other codes on the same units

  • E740 Abnormal outdoor temperature sensor (sub codes 01, 02)
  • E740 01, 02 Abnormal outdoor temperature sensor operation
  • E762 Vent pipe not detected by Vent Installation Detector (VID)
  • E762 00 Improper vent pipe installation
  • E774 00 Abnormal external safety system operation 1
  • E775 External safety device on IN_2 stops the furnace (auto reset)
  • E775 00 Abnormal external safety system operation 2
  • E782 Controller to front panel communication error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NPF installation and operation manual, p. 85. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.