Navien · Furnace
E762 Vent pipe not detected by Vent Installation Detector (VID)
What the control is telling you
The VID switch in the exhaust collar does not see the vent pipe fully inserted, so the furnace shows an error and will not run.
Applies to: NPF condensing hydro-furnace exhaust collar and vent installation detector
Likely causes
- Vent pipe not inserted the full 2-3/4 in (70 mm) into the exhaust collar
- Vent pipe is the wrong size (a correctly sized 2.0 in pipe is needed to press the switch)
- Vent pipe is damaged or deformed
- Vent pipe is misaligned or pushed up or down out of the collar
- VID switch is sticking or corroded
Test and repair steps
- Check the vent pipe is pushed fully into the collar until it bottoms out in the socket.
- Confirm the 2-3/4 in (70 mm) reference mark is no longer visible at the collar.
- Confirm the vent pipe is the correct 2.0 in size.
- Inspect the pipe for cracks or deformation and replace it if damaged.
- Make sure the pipe is square in the collar and not pushed vertically out of position.
- Tighten the clamp to seal the joint, then restart the furnace.
Other codes on the same units
- E615 04 Abnormal ADC reference voltage
- E615 05 Abnormal MCU
- E740 Abnormal outdoor temperature sensor (sub codes 01, 02)
- E740 01, 02 Abnormal outdoor temperature sensor operation
- E762 00 Improper vent pipe installation
- E774 External safety device on IN_1 stops the furnace
- E774 00 Abnormal external safety system operation 1
- E775 External safety device on IN_2 stops the furnace (auto reset)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPF installation and operation manual, p. 62. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.