Navien · Combi boiler
E777 Low water cutoff (LWCO) activated
What the control is telling you
The external LWCO device has opened (low water in the system). NFC-H manual lists the reset type as: Auto reset.
Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)
Likely causes
- Low system water level
- External LWCO wiring
- LWCO fault
Test and repair steps
- Inspect the LWCO wiring. The boiler puts out 24 VAC on the LWCO terminals (CNC3).
- Make sure the system water level/pressure is correct.
- Top up the system with make-up water as required.
- Test the LWCO per its own instructions (annual inspection may be required).
Settings for these units
- Minimum installation clearances (indoor) · Navien NCB-H
- Water quality limits (DHW and system fill) · Navien NCB-H
- Minimum installation clearances (indoor) · Navien NFC-H
- Water quality limits (DHW and system fill) · Navien NFC-H
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.