Navien · Combi boiler

E048 Low LP gas pressure (propane models)

High severity Navien CH ASME

What the control is telling you

On propane units the board flags E048 when the gas pressure sensor sees LP pressure out of range. The unit needs a manual reset once the supply is fixed.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Likely causes

  • LP tank low or empty
  • LP supply pressure too low (often in winter)
  • Gas pressure sensor (GPS) or its hose faulty

Test and repair steps

  1. Gas work licensed gas tech only.
  2. Check the LP tank level and refill if low.
  3. With the unit firing at max, check inlet pressure: LP 8-13.5 in. W.C.
  4. If supply is good, check the GPS hose for kinks or tears and check GPS voltage at CN7 (see E035 guide).
  5. Reset the unit after the fix.

Settings for these units

Models that show this code

3 models in Navien CH ASME

CH-180 ASMECH-210 ASMECH-240 ASME

Other codes on the same units

  • E022 DHW cold inlet sensor shorted
  • E027 Air pressure sensor fault
  • E028 Leak on the heating side
  • E035 Gas pressure sensor fault
  • E036 Communication failure
  • E037 Water leak inside the unit
  • E039 Flow sensor fault
  • E040 Outdoor sensor shorted

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.1 Error Code List p.55; 4.6.12 GPS p.43. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.