Navien · Combi boiler
E009 Fan motor fault
What the control is telling you
The control does not see the fan running the way it should. Fan speed is monitored and a fan problem stops the boiler.
Applies to: Navien CH-180 / CH-210 / CH-240 ASME combi boilers
Likely causes
- Dirty intake air filter
- Dirty or failing fan motor
Test and repair steps
- Reset first switch the remote controller OFF then ON, or unplug the unit and plug it back in. If the code comes back, keep going.
- Turn off power before opening the cabinet.
- Pull and clean the intake air filter (top left, above the fan, one Phillips screw).
- Check and clean the fan motor.
Settings for these units
- Minimum installation clearances (indoor) · Navien NCB-H
- Water quality limits (DHW and system fill) · Navien NCB-H
- Minimum installation clearances (indoor) · Navien NFC-H
- Water quality limits (DHW and system fill) · Navien NFC-H
Models that show this code
3 models in Navien CH ASME
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien CH ASME User's Operation Manual (ch-asme-operation-manual-en), Error Code Guide, p.42. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.