E788 Incorrect gas type setting
What the control is telling you
The gas type setting is wrong. Manual action: check DIP switch setting.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- DIP SW2 #1 does not match the gas supplied
- Gas conversion done without changing the DIP switch
Test and repair steps
- Warning: Power off before changing DIP switches.
- Set DIP SW2 #1 OFF for natural gas, ON for propane, matching the rating plate and conversion label.
- Make sure the orifice matches the gas (the LP orifice comes in the Propane Gas & High Altitude Conversion Kit).
- Check Gas (NG/LPG) in Status Info, then verify CO2 per the combustion table.
Settings for these units
Installation clearances (indoor) · Navien NHB-H
| Side | Minimum clearance |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
| Vent to combustibles | 0 in |
Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.
Common vent installs: 36 in above the top and 24 in in front are recommended for service.
Installation clearances (indoor) · Navien NFB-H
| Side | Minimum clearance |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
| Vent to combustibles | 0 in |
Do not install on carpet; indoors only.
Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.
Models that show this code
6 models in Navien NHB-H, Navien NFB-H
Other codes on the same units
- E777 Low water cutoff activated
- E782 Front panel communication fault
- E784 Zone controller communication fault
- E786 Improper front panel detected
- SH1 Thermostat Status Input/Output Status item 1 - SH1 Thermostat Status
- SH2 Thermostat Status Input/Output Status item 2 - SH2 Thermostat Status
- SH3 Thermostat Status Input/Output Status item 3 - SH3 Thermostat Status
- Zone2 Pump Status Input/Output Status item 7 - Zone2 Pump Status
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.