Navien · Boiler

E352 High water pressure

High severity Navien NHB-HNavien NFB-H

What the control is telling you

System pressure is above the high limit. Manual action: check water pressure.

Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers

Likely causes

  • Expansion tank waterlogged, undersized or isolated
  • Fill/pressure reducing valve letting by
  • System overfilled

Test and repair steps

  1. Read Water Press in Status Info and compare with the system gauge.
  2. Check the expansion tank charge and size and that it cannot be isolated from the boiler.
  3. Check the pressure reducing / make-up valve is not over-pressurizing the system.
  4. NHB-H system pressure 12-30 psi with a 30 psi relief valve. NFB-H: 12-80 psi; parameter 17 High Sys Pressure (40-80 psi, default 50 psi) should suit the relief valve rating.
  5. Drain to the correct pressure and retest.

Settings for these units

Installation clearances (indoor) · Navien NHB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.

Common vent installs: 36 in above the top and 24 in in front are recommended for service.

Installation clearances (indoor) · Navien NFB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Do not install on carpet; indoors only.

Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.

Models that show this code

6 models in Navien NHB-H, Navien NFB-H

NFB-175HNFB-200HNHB-055HNHB-080HNHB-110HNHB-150H

Other codes on the same units

  • E110 Exhaust blockage
  • E205 Heating supply temperature sensor
  • E218 Heating return temperature sensor
  • E278 External system supply sensor not detected
  • E279 External system return sensor not detected
  • E291 Return temperature higher than supply
  • E302 Low water pressure
  • E353 Water pressure sensor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.