E278 External system supply sensor not detected

Medium severity Navien NHB-HNavien NFB-H

What the control is telling you

The external system supply sensor is not connected or not read. Manual action: check sensor connections.

Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers

Likely causes

  • System supply sensor missing or unplugged at the SUPPLY terminal
  • Broken wire
  • Control set to use the system sensor (cascade, SH/DHW control method = Sys Supply) without one installed

Test and repair steps

  1. Check the sensor wires at the SUPPLY terminal of the CNT terminal strip.
  2. Cascade systems require the Navien system supply and return sensors on the main unit.
  3. If no system sensor is used, make sure SH Control Method and DHW control method are not set to Sys Supply.
  4. Check Sys Supply Temp in Status Info; replace the sensor if open.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.