Navien · Air conditioner

PC Low discharge superheat (liquid floodback risk)

High severity Navien NAA

What the control is telling you

Discharge temperature is only 5°C (9°F) or less above the coil temperature (T5 - T3).

Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)

Likely causes

  • Overcharge
  • Restriction or air in the lines
  • T3 or T5 sensor reading wrong
  • PCB fault

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Measure the T5 and T3 sensors against the 6.3 R-T Table, p.61. Replace a bad one.
  3. Restart the unit. Every minute, compare an infrared reading on the discharge line and coil with parameters 08 (T5) and 06 (T3), until it stops.
  4. Readings do not match the CHK display replace the outdoor PCB.
  5. Readings match and T5 minus T3 is not 5°C (9°F) or less: replace the outdoor PCB.
  6. T5 minus T3 really is 5°C (9°F) or less: liquid is getting back to the compressor. Look for overcharge, restriction or air in the lines.

Models that show this code

2 models in Navien NAA

NAA17V36NAA17V60

Other codes on the same units

  • LA Compressor speed held back by voltage
  • LB Compressor speed held back by high pressure
  • LC Compressor speed held back by condenser temperature
  • LD Compressor speed held back by discharge temperature
  • LE Compressor speed held back by drive module temperature
  • LF Compressor speed held back by current
  • PD High pressure too high
  • PRH Crankcase heater warm-up, no start yet

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAA Series Air Conditioner Service Manual, 3.2.17, p.42-43. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.