Navien · Air conditioner
PC, H7 Moisture exposure error (overheat, T5-T3 under 9°F / 5°C)
What the control is telling you
The system has detected moisture exposure. The check compares the discharge temperature sensor T5 with the coil sensor T3, and the unit trips when T5-T3 is 9°F (5°C) or less.
Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K
Likely causes
- Air or nitrogen mixed into the refrigerant system
- Abnormal resistance on the T5 or T3 sensor
- Parameters 6 and 8 do not match the measured temperatures
- Blockage or air mixing in the refrigerant piping
Test and repair steps
- Confirm the supply is normal at 230 V phase voltage and the motor port reads 310 VDC.
- Check that the system has no air or nitrogen and the pressure is normal. If not, evacuate, recharge refrigerant and add refrigeration oil.
- Measure the resistance of the T5 and T3 sensors. Replace any sensor that is out of range.
- Power off and restart the unit. While running, measure T5 and T3 with an infrared thermometer and read parameters 6 and 8 on the display board. Record every minute until the unit stops.
- If the measured values do not match the spot checks, replace the PCB.
- If T5-T3 is not below 9°F (5°C), replace the PCB.
- If T5-T3 is below 9°F (5°C), check the installation for pipe blockage or air in the piping.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAA air conditioner service manual, p. 42-43. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.