Mitsubishi · Heat pump

NOT AVAILABLE Remote message - function not available

Normal status Mr. Slim PEAD-RP JA(L) ducted indoor unit

What the display is showing

The wired remote displays NOT AVAILABLE when a button is pressed that operates a function this indoor unit does not have. Not a fault. If one remote runs several different indoor units, the message is not shown as long as any one of them supports the function.

Applies to: Mr. Slim PEAD-RP JA(L) ducted indoor units with PAR-21MAA wired remote

Models that show this code

14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit

PEAD-RP100JAPEAD-RP100JALPEAD-RP125JAPEAD-RP125JALPEAD-RP140JAPEAD-RP140JALPEAD-RP35JAPEAD-RP35JALPEAD-RP50JAPEAD-RP50JALPEAD-RP60JAPEAD-RP60JALPEAD-RP71JAPEAD-RP71JAL

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Mitsubishi PEAD-RP35JA(L) Service Manual, Part Names and Functions, p.4. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.