Midea · Mini-split

PC00 Inverter module (IPM) protection

Critical severity Midea DLCM(R/H)B multi-zone outdoorMidea DLFSHBH wall indoor (DLCM multi-zone)

What the control is telling you

The drive chip got a bad signal back from the IPM, so the unit shut down. Outdoor board shows P6; 48K HH shows P0.

Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)

Likely causes

  • Wiring
  • Bad IPM
  • Outdoor fan problem
  • Bad compressor
  • Bad outdoor PCB

Test and repair steps

  1. Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
  2. Check the supply is 208-230 V, 1 phase, 60 Hz and the power leads are tight.
  3. Measure DC across P and N on the IPM 277-356 V on 18-27K units, 277-410 V on 36-48K units.
  4. Check the cable between the main board and the IPM, the compressor leads, and every terminal in the electrical box.
  5. Check the bridge rectifier (no terminal pair should read 0 ohms) and each reactor lead for an open.
  6. Make sure the outdoor fan runs and the unit can breathe. If the fan is the problem, follow the fan fault (EC07).
  7. Check compressor winding resistance (should be equal on all three pairs).
  8. Replace in this order and retest each time: IPM module, outdoor main board, compressor.

Models that show this code

12 models in Midea DLCM(R/H)B multi-zone outdoor, Midea DLFSHBH wall indoor (DLCM multi-zone)

DLCMHBH24CAKDLCMHBH30DAKDLCMHBH36DAKDLCMHBH48EAKDLCMRBH18BAKDLCMRBH36DAKDLCMRBH48EAKDLFSHBH09XAKDLFSHBH12XAJDLFSHBH12XAKDLFSHBH18XAKDLFSHBH24XAK

Other codes on the same units

  • P2 Compressor top overheat (OLP)
  • P3 Low outdoor temperature cut-off in heating
  • P4 Compressor drive fault
  • P7 IPM temperature sensor fault
  • PC0A Condenser high temperature protection
  • PC0F PFC module protection
  • PC0L Outdoor temperature too low
  • PC02 Compressor top overheat (OLP)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 23 Outdoor Unit Error Display p.26; diagnosis p.41, 68; Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17, p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.