Midea · Mini-split
P2 Compressor top overheat (OLP)
What the control is telling you
Same fault as PC02. Shown on the 48K high heat model.
Applies to: DLCMHBH48EAK (48K high heat) only
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Check indoor and outdoor airflow clear the inlets, outlets and coils.
- Leave power off 10 minutes so the compressor cools, then check whether the top is still above 194 F (90 C).
- Check the overload protector (OLP) plug and wiring. With the compressor cool, the OLP should read 0 ohms; open = replace the OLP.
- Check the refrigerant side for a leak or restriction and repair.
- If OLP and system are good, replace the outdoor control PCB.
Models that show this code
7 models in Midea DLCM(R/H)B multi-zone outdoor
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 24 Outdoor Unit Error Display (48 High Heat only) p.27; diagnosis p.69. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.