Midea · Mini-split
ODU E5 Over or under voltage (outdoor board)
What the control is telling you
Outdoor board display. Indoor shows PC10/PC11/PC12 (old P1).
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Measure supply voltage L1-L2 at the outdoor unit: about 187-253 VAC is acceptable.
- Measure DC across P and N on the IPM board: 277-356 V for 18-27K, 277-410 V for 36-48K.
- On 2-3 zone units also check DC across the bridge rectifier + and -: 190-250 V is normal.
- If the supply is good, replace parts in this order and retest: bridge rectifier (4-5 zone units), IPM board, outdoor main board.
Models that show this code
7 models in Midea DLCM(R/H)B multi-zone outdoor
Other codes on the same units
- ODU E0 Outdoor EEPROM error (outdoor board)
- ODU E2 Indoor / outdoor communication error (outdoor board)
- ODU E3 IPM to main board communication error (outdoor board)
- ODU E4 Outdoor or T2B sensor fault (outdoor board)
- ODU E6 PFC module protection (outdoor board)
- ODU E8 Outdoor fan speed fault (outdoor board)
- ODU Ed Adapter / inverter board to main board communication error
- ODU F1 Zone A coil outlet sensor (T2B-A) fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 27 Outdoor Unit Digital Codes p.32; diagnosis p.52-55. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.