Midea · Mini-split

EL0C Refrigerant leak detected

High severity Midea DLFSHBH wall indoor (DLCM multi-zone)

What the control is telling you

The indoor coil (T2) did not drop at least 2 C below its start value within 5 minutes of compressor start, 3 times. Display shows EC and the unit stops.

Applies to: DLFSHBH high wall indoor units 09-24K (Midea / Carrier / Viessmann) on DLC multi-zone or single-zone outdoor units

Likely causes

  • Low charge / leak
  • T2 sensor loose or bad
  • Blockage
  • Bad indoor PCB

Test and repair steps

  1. Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
  2. Restart after 2 minutes.
  3. Feel the indoor discharge air in cooling. No cold air: check for leaks and blockages, repair and recharge.
  4. Cold air but code returns check the T2 sensor is clipped on and reads right; then replace the indoor PCB.

Models that show this code

5 models in Midea DLFSHBH wall indoor (DLCM multi-zone)

DLFSHBH09XAKDLFSHBH12XAJDLFSHBH12XAKDLFSHBH18XAKDLFSHBH24XAK

Other codes on the same units

  • EH0b Indoor PCB to display board communication error
  • EH02 Zero-crossing signal error
  • EH03 Indoor fan speed out of range
  • EH30 Indoor external fan low voltage
  • EH31 Indoor external fan over voltage
  • Eh60 Room sensor (T1) fault
  • Eh61 Indoor coil sensor (T2) fault
  • EL01 Indoor / outdoor communication error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17, p.32. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.