Midea · Heat pump
PC44 Outdoor unit zero-speed protection
What the control is telling you
The compressor shows zero speed when it should be running.
Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)
Likely causes
- Compressor locked/stalled
- Compressor wiring fault
- Drive board fault
Test and repair steps
- Warning: Turn off and lock out power at the outdoor disconnect and wait for the inverter capacitors to discharge before touching the outdoor board or compressor wiring.
- Check compressor wiring.
- Check the compressor for locked rotor (winding tests per service manual).
- Replace drive board or compressor as indicated.
Settings for these units
- Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.