Midea · Heat pump

PC40 Main chip to compressor-driver chip communication error

High severity Midea DLCURA ducted single-zone inverter heat pump (outdoor)

What the control is telling you

The outdoor main control chip has lost communication with the compressor driver chip.

Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)

Likely causes

  • Outdoor board fault
  • Loose internal connection between boards

Test and repair steps

  1. Warning: Turn off and lock out power at the outdoor disconnect and wait for the inverter capacitors to discharge before touching the outdoor board or compressor wiring.
  2. Reseat connectors between the outdoor control and drive boards.
  3. Power cycle the unit.
  4. If it persists, replace the outdoor board per the service manual.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.