Midea · Heat pump
EC07 Outdoor DC fan motor fault / speed out of control
What the control is telling you
The outdoor fan motor is not running or its speed cannot be controlled.
Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)
Likely causes
- Fan blade blocked by ice, debris or obstruction
- Fan motor connector loose
- Failed DC fan motor
- Outdoor board fan driver fault
Test and repair steps
- Warning: Turn off and lock out power at the outdoor disconnect and wait for the inverter capacitors to discharge before touching the outdoor board or compressor wiring.
- Check that the fan turns freely and is not blocked by ice, snow or debris; clear the coil and fan area.
- Reseat the fan motor plug on the outdoor board.
- Inspect the fan motor wiring for damage.
- Restart and watch the fan; replace the fan motor if it will not run with a good connection, otherwise suspect the outdoor board.
Settings for these units
Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)
| Side | Minimum |
|---|---|
| A - top | 24 in. (610 mm) |
| B - right side (service side) | 24 in. (610 mm) |
| C - front (air outlet) | 24 in. (610 mm) |
| D - left side | 4 in. (101 mm) |
| E - rear (air inlet) | 4 in. (101 mm) |
| Above max snow depth | 2 in. (50 mm) |
Side letters taken from Fig. 8 drawing.
Units facing each other: 59 in. (150 cm) or more; do not blow into another unit's inlet.
Models that show this code
12 models in Midea DLCURA ducted single-zone inverter heat pump (outdoor)
Other codes on the same units
- EC50 outdoor temperature sensor fault
- EC51 Outdoor EEPROM error
- EC52 condenser coil temperature sensor fault
- EC53 outdoor ambient temperature sensor fault
- EC54 Discharge temperature sensor (TP) open/short
- EC71 Outdoor DC fan motor over-current
- EC72 Outdoor DC fan motor lack-phase
- EL01 Indoor/outdoor communication error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.