Midea · Heat pump

EC72 Outdoor DC fan motor lack-phase

High severity Midea DLCURA ducted single-zone inverter heat pump (outdoor)

What the control is telling you

The board detects a missing phase on the DC fan motor output.

Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)

Likely causes

  • Loose or broken fan motor lead
  • Fan motor winding open
  • Board driver fault

Test and repair steps

  1. Warning: Turn off and lock out power at the outdoor disconnect and wait for the inverter capacitors to discharge before touching the outdoor board or compressor wiring.
  2. Reseat the fan motor plug on the outdoor board.
  3. Inspect the fan motor leads for a broken conductor.
  4. Check the motor windings for an open phase.
  5. Replace the fan motor or outdoor board as indicated.

Settings for these units

Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)

SideMinimum
A - top24 in. (610 mm)
B - right side (service side)24 in. (610 mm)
C - front (air outlet)24 in. (610 mm)
D - left side4 in. (101 mm)
E - rear (air inlet)4 in. (101 mm)
Above max snow depth2 in. (50 mm)

Side letters taken from Fig. 8 drawing.

Units facing each other: 59 in. (150 cm) or more; do not blow into another unit's inlet.

Models that show this code

12 models in Midea DLCURA ducted single-zone inverter heat pump (outdoor)

DLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABK

Other codes on the same units

  • EC52 condenser coil temperature sensor fault
  • EC53 outdoor ambient temperature sensor fault
  • EC54 Discharge temperature sensor (TP) open/short
  • EC71 Outdoor DC fan motor over-current
  • EL01 Indoor/outdoor communication error
  • EL16 Main board to transit board communication error
  • LC06 Inverter module (IPM) high temperature protection
  • PC00 Inverter module (IPM) protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.