Lennox · Heat pump

Green & Red simultaneous SLOW flash Normal operation or standby

Normal status Lennox EL16KP1Lennox ML14KP1

What the display is showing

Both LEDs on the demand defrost control (DS2 green, DS1 red) blink slowly together. This is the healthy state: the unit is running normally or waiting for a thermostat call. No action is needed.

Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)

Settings for these units

Outdoor unit clearances · Lennox EL16KP1

LocationClearance
Service side (one side next to control box)30 in. (762 mm)
One of the other three sides36 in. (914 mm)
One of the remaining two sides12 in. (305 mm)
Last side6 in. (152 mm)
Between two units24 in. (610 mm)
Top48 in. (1219 mm)
Above roof surface (roof mount)6 in. (152 mm) minimum

Increase clearances where snow/ice can fall on the unit or air can recirculate (decks, tight spaces).

Wind barrier, if used, 24 in. (610 mm) from the unit.

Outdoor unit clearances · Lennox ML14KP1

LocationClearance
Service side (one side next to control box)24 in. (610 mm)
One of the other three sides36 in. (914 mm)
One of the remaining two sides12 in. (305 mm)
Last side6 in. (152 mm)
Top48 in. (1219 mm)
Multi-unit, between units12 in. (305 mm) minimum [18 in. (457 mm) recommended] or 24 in. (610 mm) depending on layout
Multi-unit service side24 in. (610 mm) recommended
Above roof surface (roof mount)6 in. (152 mm) minimum

Multi-unit spacing (A/B) depends on single row, wall or multiple rows layout - see figure on p.7.

Increase clearances where snow/ice can fall on the unit or air can recirculate.

Models that show this code

14 models in Lennox EL16KP1, Lennox ML14KP1

EL16KP1-018EL16KP1-024EL16KP1-030EL16KP1-036EL16KP1-042EL16KP1-048EL16KP1-060ML14KP1-018ML14KP1-024ML14KP1-030ML14KP1-036ML14KP1-042ML14KP1-048ML14KP1-060

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, Table 4 Demand Defrost Control (A108) Diagnostic LEDs, p.32. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.