Lennox · Heat pump
Green FAST flash / Red ON Discharge line temperature lockout
What the control is telling you
Discharge temp fault happened 5 times. With the compressor running, the control shuts off its contactor output (and defrost output if on). On these units, suspect the 10K resistor used in place of a discharge sensor.
Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)
Likely causes
- Shorted 10K resistor on the discharge sensor connection
- Wiring short at the discharge sensor terminals
Test and repair steps
- Check the 10K resistor on the discharge sensor terminals for a short; replace if bad.
- Check the resistor leads for contact with each other or the board.
- To clear a 5-strike lockout after the repair, place a jumper on the TEST pins (P1) or cycle 24 VAC power to the defrost control; then put the jumper back on the desired setting.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, Table 4 Demand Defrost Control (A108) Diagnostic LEDs, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.