Kinghome · Heat pump

PL DC bus voltage low

High severity Kinghome KM HT1DIKinghome KM HF1DIKinghome Ultranixx EcoKinghome Ultranixx

What the control is telling you

The DC bus voltage is below its limit and the unit stops.

Applies to: Kinghome KM09HT1DI, KM12HT1DI, KM18HT1DI, KM24HT1DI wall mini-splits; Kinghome KM09HF1DI to KM24HF1DI wall mini-splits (Gree GFH..DA/DB); Kinghome Ultranixx Eco KD24UHO to KD60UHO outdoor units with KD..UHI air handlers; Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers

Likely causes

  • Low supply voltage (below 150 VAC on the wall units)
  • Faulty bus-voltage sampling circuit

Test and repair steps

  1. Measure supply voltage under load.
  2. Fix any supply problem.
  3. Warning: Switch off power at the breaker and wait for the DC bus capacitors to discharge before touching the outdoor control board or compressor wiring.
  4. Replace the board if supply is fine.

Models that show this code

27 models in Kinghome KM HT1DI, Kinghome KM HF1DI, Kinghome Ultranixx Eco, Kinghome Ultranixx

KD24UHIKD24UHOKD30UHIKD30UHOKD36UHIKD36UHOKD42UHIKD42UHOKD48UHIKD48UHOKD60UHIKD60UHOKM09HF1DIKM09HT1DIKM12HF1DIKM12HT1DIKM18HF1DIKM18HT1DIKM21HF1DIKM24HF1DIKM24HT1DIKU24UH2IKU36UH2IKU36UHOKU48UH2IKU60UH2IKU60UHO

Other codes on the same units

  • ON Debug menu option ON
  • Operation lamp Operation lamp lit (power connected)
  • PA AC current protection
  • PH DC bus voltage high
  • PU Capacitor charging failure
  • Pc Drive current detection error
  • SE Energy-saving mode active
  • Shielded icon Functions shielded by remote monitor

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Kinghome KM09-12-18-24HT1DI service manual, sec. 9.1 error code list; Kinghome KM09-24HF1DI service manual, sec. 11.1 error code list; Kinghome Ultranixx Eco KD24-60UHO service manual, sec. 3.3-3.4; Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 3.3-3.4. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.