KeepRite · Air conditioner
TRIP + ALERT flashing together Comfort Alert - control voltage too low to operate
What the control is telling you
Both TRIP and ALERT lights flash at the same time: control voltage is too low.
Applies to: KeepRite CXA6/HXA6/TXA6 all sizes; C4A3/H4A3/T4A3 sizes 18 and 36-60 (Comfort Alert module)
Likely causes
- Weak transformer or low line voltage
Test and repair steps
- Measure 24 V at the module.
- Check transformer and line voltage.
Settings for these units
Outdoor unit clearances · KeepRite C4A3/CXA6 AC
| Location | Minimum |
|---|---|
| Service end | 24 in. (610 mm) |
| Above unit | 48 in. (1219 mm) |
| One side | 6 in. (152 mm) |
| Other sides | 12 in. (305 mm) |
| Between units | 24 in. (610 mm); 18 in. (457 mm) with no overhang within 12 ft |
| Roof mount height above roof | 6 in. (152 mm) |
| Shrubs/fences from coil | 18 in. (457 mm) |
Keep roof run-off and snow from falling on the unit.
Unit must be level within 2 degrees.
Models that show this code
2 models in KeepRite C4A3/CXA6 AC
Other codes on the same units
- 84 High pressure lockout
- Amber 1 flash Running - cooling / low stage (normal)
- Amber LED off Standby - no call (2-wire hookup or indoor unit unpowered)
- Amber LED on solid Standby - no call (communicating)
- Green COMM LED off No communication yet
- Green COMM LED on Communication with the system established
- Green POWER LED Comfort Alert module has power
- Red TRIP LED Comfort Alert TRIP - Y call but compressor not running
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Fig. 15 Comfort Alert Diagnostics, p.13. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.