KeepRite · Air conditioner

Amber LED off Standby - no call (2-wire hookup or indoor unit unpowered)

Normal status KeepRite C4A3/CXA6 ACKeepRite *SA/*SH Single-Stage Communicating

What the display is showing

The amber status LED is dark. With only two thermostat wires (C and Y, with an R-Y jumper) the board loses power whenever there is no cooling call, so no flash codes can be shown. It also looks like this if the indoor unit has no power. Normally nothing is wrong.

Applies to: C4A3/CXA6 A-C; *SA/*SH single-stage communicating board

Settings for these units

Outdoor unit clearances · KeepRite C4A3/CXA6 AC

LocationMinimum
Service end24 in. (610 mm)
Above unit48 in. (1219 mm)
One side6 in. (152 mm)
Other sides12 in. (305 mm)
Between units24 in. (610 mm); 18 in. (457 mm) with no overhang within 12 ft
Roof mount height above roof6 in. (152 mm)
Shrubs/fences from coil18 in. (457 mm)

Keep roof run-off and snow from falling on the unit.

Unit must be level within 2 degrees.

Models that show this code

4 models in KeepRite C4A3/CXA6 AC, KeepRite *SA/*SH Single-Stage Communicating

*SA5*SA6C4A3CXA6

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite ICP C4A3/H4A3/T4A3/CXA6 A-C Installation Instructions 421 01 5103 05, Table 1 Status Codes, p.17-18 and 2-wire hookup, p.16; split service manual Table 13 p.46-47. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.