KeepRite · Air conditioner

9 Comfort Alert 9 - low control voltage

Medium severity KeepRite C4A3/CXA6 AC

What the control is telling you

Yellow ALERT, 9 flashes: control circuit under 17 VAC.

Applies to: KeepRite CXA6/HXA6/TXA6 all sizes; C4A3/H4A3/T4A3 sizes 18 and 36-60 (Comfort Alert module)

Likely causes

  • Overloaded transformer
  • Low line voltage

Test and repair steps

  1. Measure 24 V at the module.
  2. Check transformer size and loads.
  3. Check line voltage.

Settings for these units

Outdoor unit clearances · KeepRite C4A3/CXA6 AC

LocationMinimum
Service end24 in. (610 mm)
Above unit48 in. (1219 mm)
One side6 in. (152 mm)
Other sides12 in. (305 mm)
Between units24 in. (610 mm); 18 in. (457 mm) with no overhang within 12 ft
Roof mount height above roof6 in. (152 mm)
Shrubs/fences from coil18 in. (457 mm)

Keep roof run-off and snow from falling on the unit.

Unit must be level within 2 degrees.

Models that show this code

2 models in KeepRite C4A3/CXA6 AC

C4A3CXA6

Other codes on the same units

  • 3 Comfort Alert 3 - short cycling
  • 4 Comfort Alert 4 - locked rotor
  • 5 Comfort Alert 5 - open circuit
  • 6 Comfort Alert 6 - open start circuit
  • 7 Comfort Alert 7 - open run circuit
  • 16 Lost communication with wall control
  • 31 High pressure switch open
  • 45 Outdoor control board failure

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Fig. 15 Comfort Alert Diagnostics, p.13. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.