KeepRite · Air conditioner

5 Comfort Alert 5 - open circuit

High severity KeepRite C4A3/CXA6 AC

What the control is telling you

Yellow ALERT, 5 flashes: no current path to the compressor.

Applies to: KeepRite CXA6/HXA6/TXA6 all sizes; C4A3/H4A3/T4A3 sizes 18 and 36-60 (Comfort Alert module)

Likely causes

  • Disconnect, breaker or fuses open
  • Contactor failed open
  • Manual-reset high pressure switch open
  • Open compressor supply wiring
  • Long protector reset time in extreme heat
  • Damaged windings

Test and repair steps

  1. Check power through the disconnect and contactor.
  2. Reset/check any manual high-pressure switch.
  3. Check compressor wiring.
  4. Allow time for the protector to reset, then ohm the windings.

Settings for these units

Outdoor unit clearances · KeepRite C4A3/CXA6 AC

LocationMinimum
Service end24 in. (610 mm)
Above unit48 in. (1219 mm)
One side6 in. (152 mm)
Other sides12 in. (305 mm)
Between units24 in. (610 mm); 18 in. (457 mm) with no overhang within 12 ft
Roof mount height above roof6 in. (152 mm)
Shrubs/fences from coil18 in. (457 mm)

Keep roof run-off and snow from falling on the unit.

Unit must be level within 2 degrees.

Models that show this code

2 models in KeepRite C4A3/CXA6 AC

C4A3CXA6

Other codes on the same units

  • 1 Comfort Alert 1 - long run time
  • 2 Comfort Alert 2 - system pressure trip
  • 3 Comfort Alert 3 - short cycling
  • 4 Comfort Alert 4 - locked rotor
  • 6 Comfort Alert 6 - open start circuit
  • 7 Comfort Alert 7 - open run circuit
  • 9 Comfort Alert 9 - low control voltage
  • 16 Lost communication with wall control

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Fig. 15 Comfort Alert Diagnostics, p.13. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.