ICP · Furnace

4+3 Low/medium pressure switch open while medium/high switch closed

Medium severity ICP (F/G)9MAE Modulating Furnace

What the control is telling you

Pressure switch states do not make sense: a lower switch is open while a higher one is closed.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

Likely causes

  • Low or medium pressure switch stuck open
  • Disconnected or blocked pressure tubing
  • Improper pressure switch wiring
  • Low inlet gas pressure (if LGPS used)
  • Plugged condensate drain
  • Water in vent pipe (sagging)

Test and repair steps

  1. Check each pressure switch tube is connected and clear.
  2. Check pressure switch wiring against the wiring diagram.
  3. Flush collector box and clean condensate trap/drain; fix sagging vent pipe.
  4. If LGPS used, verify inlet gas pressure 4.5 to 13.6 in. w.c. (natural gas).
  5. Replace the stuck-open switch.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.