ICP · Furnace
5 Abnormal flame-proving signal
What the control is telling you
Flame is sensed while the gas valve is off. Inducer runs until the fault clears.
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Gas valve stuck open or leaking through
Test and repair steps
- Warning: Gas may be flowing with the valve de-energized - shut off the manual gas valve and power if flame is present.
- Look through the sight glass for flame with no heat call.
- Check the gas valve for leak-through; replace the valve if it is stuck open or leaking.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.34. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.