ICP · Furnace

3+5 Gas valve fault (modulating valve)

High severity ICP (F/G)9MAE Modulating Furnace

What the control is telling you

The modulating gas valve did not answer a command from the control, or power to the valve electronics was interrupted.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

Likely causes

  • Intermittent RED, YELLOW or ORANGE wire at the gas valve
  • Loose PL8 connection
  • Failed modulating gas valve or control

Test and repair steps

  1. Warning: Turn power off before checking connectors.
  2. Check RED, YELLOW and ORANGE wires and terminals at the gas valve and PL8.
  3. Run component self-test (SW1-6) - the control tests communication with the gas valve.
  4. If wiring is good and the code repeats, replace the gas valve or control (manual text is cut off here - check the service label).

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.