ICP · Furnace

3 Low pressure switch did not close or reopened

Medium severity ICP (F/G)9MAE Modulating Furnace

What the control is telling you

Low pressure switch did not prove inducer draft or reopened. If it opens during blower on-delay, blower runs for the off-delay. If it opens within 5 minutes after ignition, the next cycle is limited to maximum heat. Also the expected code when the inducer is unplugged during the pressure-switch safety check.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

Likely causes

  • Wrong vent sizing / restricted vent
  • Air leak between vestibule and blower compartment
  • Low inlet gas pressure (if LGPS fitted)
  • Disconnected or blocked pressure tubing
  • Defective or miswired pressure switches
  • Excessive wind
  • Plugged condensate drain
  • Water in vent pipe (sagging pipe)

Test and repair steps

  1. Check vent and combustion air pipes for proper size and blockages.
  2. Check pressure tubing is connected and clear; clean the collector box pressure port with a small wire.
  3. Flush the collector box and clean the condensate trap and drain; check vent pipe for sags holding water.
  4. Seal air leaks between the vestibule and blower compartment.
  5. If LGPS used, check inlet gas pressure 4.5 to 13.6 in. w.c. natural gas at maximum heat.
  6. Check pressure switch wiring.
  7. In windy locations, if the problem persists, turn SW1-3 ON to boost inducer speed.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.