Gree · Heat pump
d4 Indoor coil inlet pipe sensor open or shorted (20K)
What the control is telling you
The indoor coil inlet pipe thermistor (20K, indoor) reads open or shorted.
Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
Likely causes
- Sensor or plug fault
- Wire damage
- Board fault
Test and repair steps
- Turn off power and reseat the sensor plug.
- Measure the sensor and compare with the 20K resistance chart in the appendix.
- Replace the sensor if out of range; if good, replace the board that reads it.
Models that show this code
3 models in Gree GMV6 Mini VRF
Other codes on the same units
- C3 Main board to fan drive communication fault
- C4 Missing indoor units
- d1 Indoor main board fault
- d3 Indoor return air sensor open or shorted (15K)
- d5 Indoor coil middle pipe sensor open or shorted (20K)
- d6 Indoor coil outlet pipe sensor open or shorted (20K)
- d9 Indoor jumper cap fault
- E0 Outdoor unit fault (shown with another code)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.