Gree · Heat pump
C4 Missing indoor units
What the control is telling you
Not enough indoor units are communicating (system needs at least 50% connected capacity).
Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
Likely causes
- Indoor unit without power
- D1/D2 wiring fault
Test and repair steps
- Confirm 208/230 VAC at each indoor unit.
- Check D1/D2 wiring.
Models that show this code
3 models in Gree GMV6 Mini VRF
Other codes on the same units
- C0 Communication fault IDU/ODU/wired controller
- C1 Main board to DC-DC controller communication fault
- C2 Main board to compressor drive communication fault
- C3 Main board to fan drive communication fault
- d1 Indoor main board fault
- d3 Indoor return air sensor open or shorted (15K)
- d4 Indoor coil inlet pipe sensor open or shorted (20K)
- d5 Indoor coil middle pipe sensor open or shorted (20K)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.