Goodman · Air conditioner

Yellow ON + Red ON Compressor protector open (older ComfortNet board)

High severity Goodman/Amana ComfortNet ASXC/GSXC/DSXC

What the control is telling you

Yellow and red LEDs both steady ON, green off: no current through the run or start winding. Same as code P0 on newer boards.

Applies to: Earlier ComfortNet condensers/heat pumps with the PCBHR101-103 or PBBGR101-102 outdoor control (green, yellow and red status LEDs) - ASXC/DSXC/ASZC/DSZC revisions before the PCBHR104 change

Likely causes

  • Compressor overload open (hot)
  • Open run winding
  • Wiring fault or failed run capacitor

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Let a hot compressor cool, then retest.
  3. Check run capacitor, wiring and compressor windings.
  4. Clears after one normal cycle.

Models that show this code

23 models in Goodman/Amana ComfortNet ASXC/GSXC/DSXC

ASXC160241ASXC160361ASXC160481ASXC160601ASXC180241ASXC180361ASXC180481ASXC180601DSXC160241DSXC160361DSXC160481DSXC160601DSXC180361DSXC180481DSXC180601GSXC160241GSXC160361GSXC160481GSXC160601GSXC180241GSXC180361GSXC180481GSXC180601

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, diagnostic/status LED table (PCBHR101-103, PBBGR101-102) p.65-69. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.