Goodman · Air conditioner

Yellow 4 flashes Locked rotor (older ComfortNet board)

Critical severity Goodman/Amana ComfortNet ASXC/GSXC/DSXC

What the control is telling you

Yellow LED 4 flashes with red ON: protector tripped 4 times in a row with average run under 15 seconds; compressor locked out. Same as code 04 on newer boards.

Applies to: Earlier ComfortNet condensers/heat pumps with the PCBHR101-103 or PBBGR101-102 outdoor control (green, yellow and red status LEDs) - ASXC/DSXC/ASZC/DSZC revisions before the PCBHR104 change

Likely causes

  • Seized compressor
  • Failed run capacitor or its wiring
  • Low line voltage

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Test run capacitor and wiring.
  3. Check line voltage during start against the rating plate.
  4. Check compressor; replace if mechanically locked.
  5. To reset a lockout, interrupt the 24 VAC supply to the outdoor control (power cycle the low voltage), then retest.

Models that show this code

23 models in Goodman/Amana ComfortNet ASXC/GSXC/DSXC

ASXC160241ASXC160361ASXC160481ASXC160601ASXC180241ASXC180361ASXC180481ASXC180601DSXC160241DSXC160361DSXC160481DSXC160601DSXC180361DSXC180481DSXC180601GSXC160241GSXC160361GSXC160481GSXC160601GSXC180241GSXC180361GSXC180481GSXC180601

Other codes on the same units

  • EE Outdoor control fault - compressor relay contacts welded
  • Yellow 1 flash Low side fault / low pressure trip / low pressure lockout (older ComfortNet board)
  • Yellow 2 flashes High side fault / high pressure trip / high pressure lockout (older ComfortNet board)
  • Yellow 3 flashes Short cycling (older ComfortNet board)
  • Yellow 5 flashes Open circuit (older ComfortNet board)
  • Yellow 6 flashes Open start circuit / lockout (older ComfortNet board)
  • Yellow 7 flashes Open run circuit / lockout (older ComfortNet board)
  • Yellow 8 flashes Low or high line voltage (older ComfortNet board)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, diagnostic/status LED table (PCBHR101-103, PBBGR101-102) p.65-69. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.