Goodman · Air conditioner
Comfort Alert TRIP Red TRIP LED - call present but compressor not running
What the control is telling you
Red TRIP LED on: the module sees a Y1 call but no compressor current.
Applies to: Amana ASX13 (CA revision) and ASX14 (1CA, 1BA and 421DA revisions) condensers fitted with the 2-wire Comfort Alert module
Likely causes
- Compressor internal protector open
- Outdoor disconnect open
- Compressor breaker or fuse open
- Broken wire or bad connector
- Low pressure switch open (if fitted)
- Contactor failed open
Test and repair steps
- Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
- Check the disconnect, breaker and fuses.
- Check 24 V at the contactor coil and that the contactor pulls in; replace a failed contactor.
- Check wiring and connectors to the compressor.
- If the compressor is hot, let the protector reset; find the cause (charge, airflow, voltage).
Models that show this code
142 models in Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)
Other codes on the same units
- Comfort Alert 6 Yellow ALERT 6 flashes - open start circuit
- Comfort Alert 7 Yellow ALERT 7 flashes - open run circuit
- Comfort Alert 9 Yellow ALERT 9 flashes - low control voltage
- Comfort Alert POWER Green POWER - module has power
- Comfort Alert TRIP+ALERT TRIP and ALERT LEDs flashing together - control voltage too low
- Comfort Alert last alert recall Last alert code replayed after power-up
- CoreSense 1 Yellow 1 flash - long run time (low side)
- CoreSense 2 Pressure trip - yellow 2 flashes (red 2 = lockout)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) - Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt - section Diagnostics Table: 2-Wire Comfort Alert Module. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.