Goodman · Air conditioner

Comfort Alert TRIP Red TRIP LED - call present but compressor not running

High severity Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)

What the control is telling you

Red TRIP LED on: the module sees a Y1 call but no compressor current.

Applies to: Amana ASX13 (CA revision) and ASX14 (1CA, 1BA and 421DA revisions) condensers fitted with the 2-wire Comfort Alert module

Likely causes

  • Compressor internal protector open
  • Outdoor disconnect open
  • Compressor breaker or fuse open
  • Broken wire or bad connector
  • Low pressure switch open (if fitted)
  • Contactor failed open

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Check the disconnect, breaker and fuses.
  3. Check 24 V at the contactor coil and that the contactor pulls in; replace a failed contactor.
  4. Check wiring and connectors to the compressor.
  5. If the compressor is hot, let the protector reset; find the cause (charge, airflow, voltage).

Models that show this code

142 models in Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)

ANX130181ANX130241ANX130301ANX130361ANX130421ANX130481ANX130601ANX130611ANX140181ANX140191ANX140241ANX140251ANX140301ANX140361ANX140371ANX140421ANX140431ANX140481ANX140601ASX130181ASX130241ASX130301ASX130361ASX130421ASX130481ASX130601ASX130611ASX140181ASX140191ASX140241ASX140251ASX140301ASX140311ASX140361ASX140371ASX140421ASX140431ASX140481ASX140601ASX160181ASX160241ASX160301ASX160311ASX160361ASX160371ASX160421ASX160481ASX160601ASX160611ASX180**1ABASXH5***10DSX160241DSX160361GSX110903GSX110904GSX111203GSX111204GSX130181GSX130241GSX130301

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) - Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt - section Diagnostics Table: 2-Wire Comfort Alert Module. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.