Daikin · Heat pump

E41 Low refrigerant

High severity Daikin FIT DH6VS/DH7VSA

What the control is telling you

Thermostat shows 41, outdoor board display shows E41. The control has decided the system is low on refrigerant.

Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Refrigerant leak
  • Low charge
  • Thermistor bad or not plugged in right

Test and repair steps

  1. Refrigerant work only by a certified tech. This unit runs on an A2L refrigerant: no open flame near a leak.
  2. Leak test the system and fix any leak.
  3. Check the charge and adjust.
  4. Check the thermistor plugs.

Models that show this code

11 models in Daikin FIT DH6VS/DH7VSA

DH6VS*181DH6VS*241DH6VS*301DH6VS*361DH6VS*421DH6VS*481DH6VS*601DH7VSA2410DH7VSA3610DH7VSA4210DH7VSA4810

Other codes on the same units

  • E37 Control board may need replacing (fan motor link)
  • E38 Compressor voltage problem
  • E39 Control board may need replacing (thermistor input)
  • E40 Compressor setup does not match the unit
  • E42 Low supply voltage
  • E43 High supply voltage
  • E44 Outdoor temperature out of operating range
  • E47 System verification test blocked by indoor heat

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.44 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.