Daikin · Heat pump
77 Indoor unit - thermostat communication error (start-up and during operation)
What the control is telling you
The thermostat is not recognized on the node list for 60 seconds after a node list is received.
Applies to: EEV air handler, EEV cased coil
Likely causes
- Incorrect wiring between indoor unit and thermostat. The system may show this communication error without code 77 on the indoor control board.
- Thermostat failure
- Power interruption (low voltage)
- Thermostat or control board failure
Test and repair steps
- Turn off the power switch before connecting or disconnecting any connector.
- Check the wiring between the indoor unit and the thermostat and correct any faults.
- Confirm the outdoor unit, gas furnace or modular blower has power.
- Press the LEARN button on the control board for more than 5 seconds to re-establish the network.
- If the error clears and does not return, no further action is needed.
- If the error returns, replace the thermostat or the control board.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin SiUS612209EA service instructions, p. 69. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.