Daikin · Heat pump

76 Indoor-outdoor, gas furnace or blower communication error (during operation)

Medium severity DX6VS / DZ6VSDV**FEC / DFVE**CAPE(A)* / CHPE*

What the control is telling you

The outdoor unit, gas furnace or modular blower drops off the node list after the system has reached system matching state.

Applies to: EEV air handler, EEV cased coil

Likely causes

  • Open communication circuit
  • Incorrect wiring between the outdoor unit, gas furnace or modular blower
  • No power to the outdoor unit, gas furnace or modular blower
  • Control board failure

Test and repair steps

  1. Turn off the power switch before connecting or disconnecting any connector.
  2. Check that the communication circuit is connected. Connect it if not.
  3. Check the communication wiring and correct any miswiring.
  4. Confirm the outdoor unit, gas furnace or modular blower has power. Restore power if not.
  5. If all of the above are correct, replace the control board.

Other codes on the same units

  • 77 Indoor unit - thermostat communication error (start-up and during operation)
  • 78 Indoor unit - outdoor unit, gas furnace or blower unit communication error (startup operation)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 68. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.