E38 Compressor voltage problem

High severity Daikin FIT DC6VS/DC9VSA

What the control is telling you

Thermostat shows 38, outdoor board display shows E38. The control sees a voltage problem on the compressor side.

Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Supply voltage too high or too low
  • Lost phase on the compressor wires
  • Bad control board

Test and repair steps

  1. Kill power at the disconnect before opening the control box or touching wiring.
  2. Measure supply voltage. Call the utility if it is out of range at the disconnect.
  3. Check the compressor wires between the board and the compressor.
  4. Replace the board if voltage and wiring are good.

Models that show this code

10 models in Daikin FIT DC6VS/DC9VSA

DC6VS*181DC6VS*241DC6VS*301DC6VS*361DC6VS*421DC6VS*481DC6VS*601DC9VSA2410DC9VSA3610DC9VSA4810

Other codes on the same units

  • E34 High current detected
  • E35 High current, possible short circuit
  • E36 Abnormal start-up
  • E37 Control board may need replacing (fan motor link)
  • E39 Control board may need replacing (thermistor input)
  • E40 Compressor setup does not match the unit
  • E41 Low refrigerant
  • E42 Low supply voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.44 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.