Daikin · Air conditioner
E24 High pressure switch open
What the control is telling you
Thermostat shows 24, outdoor board display shows E24. The high pressure switch is open.
Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- High pressure switch not working
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- Measure the high pressure switch resistance. Replace the switch if it reads open when it should be closed.
Models that show this code
10 models in Daikin FIT DC6VS/DC9VSA
Other codes on the same units
- E20 Outdoor EEV fault
- E21 Repeated low discharge superheat faults
- E22 Repeated high discharge temperature faults
- E23 Discharge temperature sensor out of range
- E25 Outdoor air temperature sensor open or shorted
- E26 Pressure sensor not responding
- E27 Outdoor coil defrost sensor out of range
- E28 Outdoor coil temperature sensor out of range
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.43 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.