Carrier · Mini-split
FH CC Refrigerant sensor error
What the control is telling you
The indoor unit receives a fault signal from the refrigerant sensor for 10 s, or it gets no feedback from the sensor for 150 s.
Applies to: D5FSFAH
Likely causes
- Refrigerant sensor fault
- Sensor wiring or connection fault
- ENC1 setting incorrect
- Indoor main PCB fault
Test and repair steps
- Shut off the power and turn it on 2 minutes later.
- If the code still shows, check that ENC1 is correct and reset ENC1 if needed.
- Check the connection between the refrigerant sensor and the PCB. Ensure proper connections.
- Replace the sensor if the fault remains.
- If the fault still exists, replace the indoor main PCB.
Models that show this code
3 models in D5FSFA
Other codes on the same units
- EH 3b External fan DC bus voltage too high
- EH 62 Indoor temperature sensor open or shorted
- EH 65 Indoor temperature sensor open or shorted
- EH 66 Indoor temperature sensor open or shorted
- EH C1 Refrigerant sensor detects leakage
- EH C2 Refrigerant sensor out of range and leakage detected
- EH C3 Refrigerant sensor out of range
- FL 09 Mismatch between new and old platforms
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier D5FSFAH service manual, p. 44. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.