Carrier · Heat pump
46 Brownout
What the control is telling you
Amber STATUS light flashes 46. Line voltage fell too low (under about 187 V for 4 s). Compressor and fan stop and stay off until voltage is back to at least 190 V. Type: Local; reset: 6 minutes.
Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8 (AOC control + inverter)
Likely causes
- Low supply voltage
- Bad connection on L1 / L2
- Inverter not reading voltage correctly
Test and repair steps
- Measure line voltage at the unit; it should be above about 180-190 V. If it stays low, contact the utility.
- Check line and load side connections on L1 and L2.
- If voltage and connections are good, replace the inverter.
Models that show this code
15 models in Carrier Infinity 18VS 25VNA8, Carrier 2-stage 24ANB/25HNB
Other codes on the same units
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.