Viessmann · Boiler · Other

Cascade communication loss (emergency operation)

Vitodens 200-W B2HE

What happens, in order

  1. Boilers in a CAN bus cascade normally follow the lead boiler
  2. If communication to the lead boiler fails, each boiler keeps using the last value it received for 60 seconds
  3. After 60 seconds each boiler runs on its own to a fixed emergency flow setpoint (only if emergency operation is enabled)
  4. Boiler frost protection monitoring stays active the whole time (boiler temperature below 41 F / 5 C)

Timings and thresholds

ItemValue
Changeover time60 s
Emergency setpoint default140 F (60 C), range 32-176 F
Emergency operation defaultdisabled

Applies to: Vitodens 200-W B2HE cascades

Models

B2HE-85B2HE-120B2HE-150B2HE-199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HE service manual (DHW and boiler function parameters, cascade emergency operation). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.