Navien · Water heater · Startup
Cascade communication set-up
What happens, in order
- Complete the cable connections and DIP switch settings first.
- Power on; each FND1 display shows the master set-up.
- Hold SW3 and SW4 on slave 1 together for more than 3 seconds; its FND1 changes to S001.
- Repeat for slave 2.
- Hold SW3 and SW4 on the master together for more than 3 seconds; all FND displays change to the setting temperature.
Timings and thresholds
| Item | Value |
|---|---|
| Hold SW3 and SW4 on each slave to start slave set-up | more than 3 seconds |
| Hold SW3 and SW4 on master to finish set-up | more than 3 seconds |
Applies to: Cascade systems
Models
CRCC
Related
Navien error codes · Navien tips · Navien parts · All Navien sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: CR-CC installation manual, p. 37. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.