Navien · Boiler · Other

Air handler contacts open (NHB-H)

NHB-H

What happens, in order

  1. Boiler is running with the air handler interface enabled (PCB DIP switch bank 2, switch 7 ON)
  2. Air handler contacts (A/H) close only while the boiler is doing space heating on a thermostat call
  3. A/H contacts open when the thermostat is turned off
  4. A/H contacts open while the boiler is making domestic hot water or is waiting in standby for a DHW call
  5. A/H contacts open on a level 2 or higher error
  6. A/H contacts open when the boiler is switched off

Applies to: NHB-H condensing boilers

Models

NHB-H

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NHB-H installation manual, air handler interface section. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.