Mitsubishi · Mini-split · Startup

Test run with wireless remote

PEAD-RP JA(L) ceiling-concealed indoor unit

What happens, in order

  1. Power the unit at least 12 hours before the test run
  2. Start from remote display off; press TEST RUN twice in a row; TEST RUN and current mode show
  3. Press MODE to select COOL and check cold air blows out
  4. Press MODE to select HEAT and check warm air blows out
  5. Press FAN and check the speed changes
  6. Press VANE and check the auto vane moves
  7. Press ON/OFF to stop the test run
  8. Point the remote at the indoor receiver for all steps; FAN, DRY and AUTO modes cannot be used in the test

Timings and thresholds

ItemValue
Pre-power time12 hours minimum

Applies to: Mitsubishi PEAD-RP35JA(L) indoor unit

Models

PEAD-RP35JA(L)

More Mitsubishi mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Mitsubishi PEAD-RP35JA(L) service manual, Test run (wireless remote controller). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.