Freezing and overheating protection (P6)

PEAD-RP JA(L) ceiling-concealed indoor unit

What happens, in order

  1. Cooling if the pipe temperature stays under -15 C for 3 minutes after the compressor starts, the unit shuts down in a 6 minute restart-prevention mode
  2. If the pipe drops under -15 C for 3 minutes again within 16 minutes of that restart, the fault P6 is declared
  3. Heating if the pipe temperature goes over 70 C after the compressor starts, the unit goes into the 6 minute restart-prevention mode
  4. If over 70 C is seen again within 10 minutes of that restart, P6 is declared
  5. Typical causes to check dirty filter, blocked air path, wrong load, indoor fan motor or board, outdoor fan control, overcharge, refrigerant circuit clog

Timings and thresholds

ItemValue
Freeze triggerpipe under -15 C for 3 min
Freeze repeat window16 min
Overheat triggerpipe over 70 C
Overheat repeat window10 min
Restart-prevention6 min

Codes you may see during this

P6 P8

Applies to: Mitsubishi PEAD-RP35JA(L) indoor unit

Models

PEAD-RP35JA(L)

More Mitsubishi mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Mitsubishi PEAD-RP35JA(L) service manual, Self-diagnosis action table P6. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.