KeepRite · Air conditioner · Cooling

Split A/C: cooling cycle with standard thermostat or communicating control

C4A3H4A3T4A3CXA6

What happens, in order

  1. Thermostat makes R-Y and R-G on a call for cooling
  2. R-Y energizes the contactor, starting outdoor fan and compressor
  3. R-G energizes the indoor blower relay, starting the indoor blower on high speed
  4. Thermostat satisfied contactor and blower relay drop out and compressor and fan stop
  5. If the indoor unit has a time-delay relay the blower runs 90 s more
  6. With a communicating wall control the outdoor board applies a 5 minute start delay; with a 2-wire hookup this delay is only 10 s
  7. Outdoor fan keeps running 1 minute after the compressor stops if outdoor air is 100 F or higher

Timings and thresholds

ItemValue
Start delay (communicating)5 min
Start delay (2-wire)10 s
Brown-out recycle delay5 min
Indoor blower run-on (with TDR)90 s
Fan run-on at 100 F+ outdoor1 min
Return to standby after last communication2 min

Codes you may see during this

16

Applies to: KeepRite / ICP C4A3, H4A3, T4A3, CXA6 R-410A split air conditioners

Models

C4A3H4A3T4A3CXA6

More KeepRite air conditioner sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP C4A3-H4A3-T4A3-CXA6 air conditioner installation instructions 421 01 5103 05, Sequence of Operation and Control Functions. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.