Lennox · Heat pump troubleshooting
Outdoor unit will not start - Lennox EL16KP1 / ML14KP1
What is going on
Thermostat calls for heat or cooling but the outdoor compressor and fan do not run.
Likely causes
- 5-minute anti-short-cycle delay
- No 24 VAC to the defrost control or no Y1 call
- Pressure switch lockout (5 strikes)
- Compressor thermal protection (S173) or internal overload open
- Contactor K1 not pulling in
- No line voltage
Check in this order
- Read the defrost control LEDs both off = no 24 VAC; alternating slow flash = 5-minute delay (jumper TEST pins to skip); red or green steady/flashing = pressure or sensor fault (see LED codes).
- Check 24 VAC between R and C and on Y1 from the thermostat.
- Check that Y1 OUT energizes the compressor contactor K1 and that K1 closes.
- Check line voltage at the disconnect; it must be within the nameplate range (operating range is +10% / -5% of rated voltage).
- If locked out, fix the cause and clear the lockout with the TEST pins or by cycling 24 VAC.
- If the compressor is hot, give the internal or S173 thermal protector time to reset.
- After a long power outage in cold weather, leave the thermostat on Emergency Heat for about 6 hours so the crankcase heater can warm the compressor before restarting the heat pump.
Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, System Operation p.26, Table 3 p.29, Test Pins p.31, Table 4 p.32, Operating Sequence and Start-Up p.37. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.