Defrost not working - test the defrost board

What is going on

Time/temperature defrost board: interval 30/60/90 min (factory 90). Defrost thermostat closes at 32F (0C) and opens at 65F (18C). Defrost limited to 10 minutes.

Likely causes

  • Defrost thermostat open or loose on its tube stub
  • Wrong interval jumper
  • Failed defrost board

Check in this order

  1. Confirm the defrost thermostat is tight on the tube stub at the coil end plate.
  2. Check the defrost thermostat 24 V across DFT = open, 0 V = closed. Or jumper the DFT terminals to bypass it.
  3. If open, force frost power off, disconnect fan lead at OF2 and tape it, run in heat until 0 V across DFT, then power off and reconnect OF2.
  4. Run in heat with DFT closed; short the SPEEDUP pins until the reversing valve shifts (normally 1-21 seconds).
  5. In defrost the reversing valve shifts, outdoor fan stops and strip heat comes on.
  6. Remove the short right away for a short defrost (ends at 65F or timer); holding it more than 2 seconds after the shift returns the unit to heating.
  7. Unit must return to heat valve shifts back, fan restarts, strip heat off. If not, replace the board.

Applies to: ICP N4H3 R-410A split heat pump (manual 428 01 5103 02); Comfort Alert codes apply only to units factory-fitted with the Comfort Alert module

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ICP N4H3 Installation Instructions 428 01 5103 02, Defrost System, p.13-14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.